Synchro-Check ( parallelling ) Relay

Synchro-Check ( parallelling ) Relay

Print document
  • Model:

    256-PLL , 256-PLD

  • Request Code:

    256-PLL , 256-PLD

  • Company:

    Ziegler

  • Country:

    Germany

  • Rate:
  • 3.0
  • From
  • 5
  • Votes:
  • 1
  • Visit Times:
  • 594

The synchro-check relay can be used to assist in the semi-automatic parallelling of two AC power systems . The volt-free relay contacts change state when the voltage level, phase relationship and frequency are within the selected synchronising limits . Connecting two electrical systems that are not closely matched can cause expensive damage and disturbance to the electrical system. Using this relay will ensure that damage will not occur . Other features of this device are : - Single phase or three phase, 3 or 4 wire - Live and dead bus versions - Adjustable setpoint - LED trip indication - Volt free relay contacts Bornika is the exclusive agent of Ziegler company in the fields of consultation , sales and distribution of power industry products including Synchro-Check (parallelling) Relay .

Specifications
  • Output 1 pair NO (normally open), 1 pair NC (normally closed) 2 pair NO and 2 pair NC (available on request)
  • Frequency Range 45 , 50 , 55 , 60 , 65 Hz
  • IP IP50
  • Dimensions 150x70x112 mm
  • Nominal Voltage 100V, 110V, 120V, 208V, 220V, 230V, 240V, 277V, 380V, 400V, 415V, 440V , 480V
  • Burden Bus : 2VA , Generator : 4VA
Price List

If you want to access to our price list,

You may login to our site: or

Or contact numbers in order to get informed about:

Tel: +98 21 66754321
Email: و

Downloads

Download catalog file: Synchro-Check (parallelling) Relay catalog 138 KB

More Details
  • Synchro-Check (parallelling) Relay
  • 256-PLL : The relay continuously monitors the voltage, phase displacement and frequency of two supplies. A single setpoint adjustment permits selection of suitable matching , and a red LED illuminates when the relay is energised , indicating that the two supplies are well matched and it is safe to close the breaker. 256-PLD : This version operates in the same way as model 256-PLL , but includes an additional dead bus detection function. If there is a requirement for a continuous supply or emergency power, then the generator can be connected without synchronising, thus ensuring continuity of supply . The absence of bus voltage will cause the relay to energise . - Operating temperature : 0°Cto +60°C - Material : Flame retardant polycarbonate/ABS - Enclosure style : DIN-rail with wall mounting facility Applications : Marine panels , Switchgear , Distribution systems , Generator sets , Co-generation , Control panels
Applications
  • Refinery
  • Electronics industry
  • Power industry
  • Packaging Industry
  • Petrochemical industry
  • Automotive industry
  • Marine and shipbuilding industry
  • Road Construction industry
  • Food industry
  • Telecommunications industry
  • Military and defense industry
  • Oil and gas industry
  • Power Plant industry
  • Panel building companies
  • Steel industry
  • Instrumentation Companies
  • Textile industry
  • Education and Laboratory industry
  • Publishing and Printing industry
  • Rubber and plastics industry
  • Manufacturing of metal products
  • Machinery and equipment industry
  • Industrial machinery, electrical appliances
  • Manufacturing of radio, television, communication devices and gauging devices
  • Measurement devices, medical and optical industry
  • Sugar industry
  • Materials and pharmaceutical products industry
  • Chemical products industry
  • The computer industry and related activities
  • Engineering services industry
  • Building industry
  • Tile and Ceramic industry
  • Cement, lime and plaster industry
  • Transport, warehousing and communications industry
  • Railway and subway industry
  • Meteorological industry
  • Aerospace Industry
  • Automation industry
  • Charger, inverter and converters manufacturers
  • Cathodic protection companies
  • Transformer manufacturing companies