Current Imbalance Guards

KPC110

    • Model
    • KPC110x

    • Order code
    • KPC110

    • Country
    • Norway
  • The digitally controlled KPC110x monitor and convert the three current transformer (CT) inputs into a signal proportional to the difference between the HIGHEST and the LOWEST input level. The difference (imbalance) is displayed as a percentage of the CT rating. 1A secondary class 0.5 transformers should preferably be used. The standard scale range is 0 to 40%CT. Special features: -2-level AC Current Imbalance Protection -True RMS measurement not affected by heavily distorted waveforms -3 or 4-wire systems. Definite time trip delays -Fast analogue mA output (F version) -Total processing time less than 50mS Bornika is the exclusive representative of megacon company, in purchasing , sales, consulting and distribution of industrial equipment including Current Guards AC.

  • Visits: 0
Downloads
Specifications
    • Power Supply
    • 100-120V, 200-240V, 380-415V, 440-460 or 480VAC 40-70Hz (Fuse 2A) Optional Auxiliary: 24, 48 or 110VDC (Fuse 0,5A)

    • Nominal input current
    • 1A CT or 5A CT

    • Contact rating
    • AC: 100VA -250V/2A max. DC: 50W -100V/1A max.

    • Output
    • Analogue outputs: Up to 20mA, max 500ohm Up to 10V, min 100kohm

    • Connection
    • -20 to +70ºC

    • Approximate Weight
    • 0.6kgs

    • IP
    • IP52 (IP65 optional)

    • Dimensions
    • 92x96x115mm

Prices