Earth fault impedance module

MML15x

    • Model
    • MML15

    • Order code
    • MML15x

    • Country
    • Norway
  • MML15xx provides a normalised earth fault leakage current return path in IT-networks. By providing a normalised earth fault leakage current return path, MML15xx improves accuracy and sensitivity of a earth fault monitoring system. special features: -Earth Fault Impedance module -For AC networks up to 690V -For use in IT-network together with Megacon's Earth Current Measuring units -DIN rail mounted Borna niroo karan company (Brnika) is Exclusive Representative of Megacon , in the purchase, sales, consulting and distribution and industrial equipment and measurement equipment, including earth fault monitoring is active .

  • Visits: 17
Downloads
Specifications
    • Operative voltage
    • 100-240V AC 380-460V AC 660-690V AC 50/60 Hz (fuse 4A)

    • Approximate Weight
    • Up to 460V: 0.3kgs Over 460V: 0.5kgs

    • Operating Temperature
    • -20 to +70ºC

    • IP
    • IP41

More details
  • Models:
  • MML1502C : 100-240VAC MML1503C : 380-460VAC MML1506C : 480-690VAC
  • Current load:
  • App. 0,2/0,3A at 50/60Hz (with clean sine wave)
Prices